Ohkura |
Omron |
Fuji |
Yokogawa M&C |
|
Products |
EC5600S |
E5AK-T |
PVX |
UP550 |
|
Input |
TC: 23 type, Pt100: 5 type, JPt100: 5 type, mV: 3 type, V: 2 type, mA 1 type |
TC: 12 type, Pt100: 1 type, JPt100: 1 type, V: 3 type, mA 2 type |
TC: 11 type, Pt100: 8 type, JPt100: 7 type, mV: 2 type, V: 4 type, mA 1 type |
TC: 14 type, Pt100: 3 type, JPt100: 2 type, mV: 2 type, V: 4 type |
|
Resolution (digit) |
4 |
4 |
4 |
5 |
|
Accuracy (%) |
±0.2 |
±0.2 to 0.3 |
±0.2 |
±0.1 to 0.2 |
|
Control Evaluation Cycle (second) |
0.1 |
0.25 for T/C input, 0.1 for mA, V input |
0.1 |
0.1 max. |
|
Output |
Multioutput (1 point)
Relay: 1a 250VAC 3A
SSR: 15VDC 20mA
Current: 4 to 20mADC or 0 to 5mADC
(Nonselective with multioutput function) |
Output unit method (sold separately)
Relay: 250 VAC 5A
SSR: 75 to 250VAC 1A
Current: 4 to 20mADC
0 to 20mADC
Voltage: 12VAC 40mA
24VAC 20mA
0 to 10VDC
0 to 5VDC |
To be specified in ordering
Relay: 1c 220VAC 3A
SSR: 10 to 18VDC 20mA
Current: 4 to 20mADC |
Multioutput (1 point)
Relay: 250VAC 3A or 30VDC 3A
SSR: 12VDC 30mA
Current: 4 to 20mADC
0 to 20mADC
20 to 4mADC
20 to 0mADC |
|
Dual Output |
Option |
Available with output device sold separately |
None |
Option |
|
Program Capacity |
16 pattern max. 189 step, 63 step per pattern |
8 pattern x 16 step |
9 pattern x 20 step |
30 pattern, 300 step, 99 step max. per pattern |
|
DO |
Alarm + DO 4 point
Option 8 point |
Alarm 2 point |
Alarm 2 point
Option 2 point |
Alarm + DO 7 point |
|
DI |
Standard 4 point, Option 7 point |
4 point, but 2 point with communication |
4 point |
Standard 7 point, option 1 point |
|
Multi-setpoint |
Multi PID: 8
Programmed PID (Reference point: 3) |
None |
Multi PID: 9 |
Multi PID: 8
Programmed PID (Reference point: 6) |
|
AO |
4 to 20mA / 0 to 20mADC (Option) |
4 to 20mADC |
2 point (Option) |
4 to 20mADC 2 point, 2 outputs, nonselective with sensor power supply |
|
Communication Interface |
RS-232C / RS-422A
(Required interface module sold separately)
ARCNET (Option) |
RS-232C / RS-422 / RS-485
(To be specified in ordering) |
Option
RS-232C / T-rink (Custom Network) |
RS-485
(To be specified in ordering) |
|
Servo Drive |
Option |
To be advised applicable spec. of PDU or other device by ordering |
None |
To be advised applicable spec. of PDU or other device by ordering |
|
Heater Break Detection |
Option (Extended I/F+ZE7201 required) |
Available with ON/OFF output model |
None |
None |
|
Outside Dimensions (mm) |
96x96x114.9 (Length of dial excluded) |
96x96x113.5 |
96x96x185.5 |
96x96x111 |
|
Features |
Self Tuning (Option),
Antiovershoot Dial Setting,
LCD Graphic Dislay,
Sensor Power Supply (Option) |
EN Standard (CE Marking) approved,
Water-proof (NEMA4) |
Three digital display |
Antiovershoot Full dot LCD graphic display,
Dust-proof, Drip-proof (IP55),
Sensor power supply (unavailable when dial output or AO is specified),
Light-loader available |