Ohkura |
Omron |
Fuji |
Yokogawa M&C |
|
Products |
EC5500S |
E5AK-A |
PYX9 |
UP350 |
|
Input |
TC: 23 type, Pt100: 5 type, JPt100: 5 type, mV: 3 type, V: 2 type, mA 1 type |
TC: 12 type, Pt100: 1 type, JPt100: 1 type, V: 3 type, mA 2 type |
TC: 11 type, Pt100: 1 type, JPt100: 1 type, V: 2 type, mA 1 type |
TC: 14 type, Pt100: 3 type, JPt100: 2 type, mV: 2 type, V: 4 type |
|
Resolution (digit) |
4 |
4 |
4 |
4 |
|
Accuracy (%) |
±0.25 |
±0.2 to 0.3 |
±0.5 |
±0.1 to 0.2 |
|
Control Evaluation Cycle (second) |
0.1 |
Temperature input 0.25 V, mA 0.1 |
0.5 |
0.25 |
|
Output |
Multioutput (1 point)
Relay: 1a 250VAC 3A
SSR: 15VDC 20mA
Current: 4 to 20mADC |
Output unit method (sold separately)
Relay: 250VAC 5A
SSR: 75 to 250VAC 1A
Current: 4 to 20mADC
0 to 20mADC
Voltage: 12VAC 40mA
24VAC 20mA
0 to 10VDC
0 to 5VDC |
Multioutput (1 point)
Relay: 1c 220VAC 3A
SSR: 24VDC 20mA
Current: 4 to 20mADC |
Multioutput (1 point)
Relay: 250VAC 3A or 30VDC 3A
SSR: 12VDC 30mA
Current: 4 to 20mADC |
|
Dual Output |
Option |
Available with output device sold separately |
Option (Unavailable when multi-output is specified) |
Option (Unavailable when No. 3 alarm, or AO, sensor power supply is specified) |
|
DO |
Alarm + DO 4 point |
Alarm 2 point |
Alarm 2 point (Option) |
Alarm 3 point |
|
DI |
4 point |
4 point, but 2 point with communication |
None |
2 point |
|
Multi-setpoint |
Multi SP: 8
Multi PID: 8 |
None |
None |
Multi SP: 4, Multi PID: 4
Programmed PID (Reference point: 2) |
|
Remote Setpoint |
1 to 5V / 0 to 5VDC (Option) |
4 to 20mADC |
1 to 5VDC (Option) |
None |
|
AO |
4 to 20mA / 0 to 20mADC (Option) |
4 to 20mADC |
1 to 5VDC (Option) |
4 to 20mADC 2 point, 2 outputs, nonselective with sensor power supply |
|
Communication Interface |
RS-232C / RS-422A
(Required interface module sold separately)
ARCNET (Option) |
RS-232C / RS-422 / RS-485
(To be specified in ordering) |
None |
RS-485 (Option) |
|
Servo Drive |
Option |
To be advised applicable spec. of PDU or other device by ordering |
None |
None |
|
Heater Break Detection |
Option (Extended I/F+ZE7201 required) |
Available with ON/OFF output model |
Option |
Option (External heater-break sensor required) |
|
Outside Dimensions (mm) |
96x96x112.4 (Length of dial excluded) |
96x96x113.5 |
96x96x112 |
96x96x111 |
|
Features |
Self Tuning (Option),
Antiovershoot Dial Setting |
EN Standard (CE Marking) approved,
Water-proof (NEMA4) |
Antiovershoot |
Antiovershoot,
Dust-proof, Drip-proof (IP55),
Sensor power supply (unavailable when dial output or AO is specified) |